| Module Specifications


No.

Part Number

WDLFP-100KW-150KWh Cabinet

1

Energy storage

10.75KWh

2

Rated Voltage

51.2V/DC

3

Capacity

210Ah

4

Maximum Charge Voltage

57.6V/DC

5

Discharge Cut-off Voltage

44.8V/DC

6

Configuration

16S7P

7

ESR/AC @1KHz 50% SOC

<10mΩ

8

Continuous Current

140A

9

Max. Power

7.15kW

10

Charge Temperature

0℃~+55℃

11

Discharge Temperature

-20℃~+60℃

12

Recommended Depth of Discharge

5%~90%

13

Maximum Depth of Discharge

100%

14

Operating Humidity

0~90% RH Non-condensing

15

Cells Self-discharge Rate

3% per month

16

Cooling Method

natural cooling

17

Shell Material

Metal

18

Communicate Method

CAN

19

Monitoring Data

Module voltage,SOC,SOH,current,temperature,cell’s voltage

20

Output Terminal

Amphenol

21

Weight

85Kg

22

Dimensions(W*D*H)

750*740*120mm


| Module Drawing


| Caprack String Specifications 716.8V150KWh


No.

Part Number

WDLFP-716.8V100KW/150KWh-R

1

Energy storage

150.5kWh

2

Rated Voltage

716.8V/DC

3

Maximum Charge Voltage

806.4V/DC

4

Discharge Cut-off Voltage

627.2V/DC

5

Configuration

16S7P* 14sets above module series connection

6

ESR/AC @1KHz 50% SOC

<140mΩ

7

Max. Continuous Current

140A

8

Max. Power

78.7KW

9

Weight

1308Kg

10

Dimensions(W*D*H)

810*750*1950mm


| Rack String Dimensions and Layout


| Caution


  •  Place the module out of the reach of children and infants.

  •  Do not place the module in microwave ovens or other similar appliances.

  •  Do not remove the product label.

  •  Do not attempt to open or service the battery pack.

  •  Do not expose to temperatures above 80℃.

  •  Do not short-circuit the positive and negative terminals of the battery with wire or other metallic objects.

  •  Do not transport or store the module with metallic items.

  •  Do not expose the module to direct heat or flame, and do not use or store it near a fire or a location, subject to high temperatures. In addition, do not immerse or dampen the module in water, saltwater, or any other liquid.

  •  Do not puncture the module with any sharp objects, hit it with a hammering device or similar device, step on it, drop it or subject it to strong shock.

  •  Do not use module if it is damaged or deformed.

  •  Immediately cease use of the module if it produces strange smells or smokes or becomes abnormally hot.

  •  If the module fluids leak and come into contact with an eye, do not rub the eye and immediately flush it with plenty of water before seeking medical assistance.


Notes

  •  The pictures in the file are only for reference.

  •  We reserve the final explanations of the items in this specification. This proposal is applicable for prototype.

  •  Specifications subject to change without notice


Previous: 
Next: 

Recommended Products

Leading Supplier Of Safe, Durable, Innovative Batteries For Green Mobility And Energy Power Storage System.
 
Add: No.71 Luda Road, Pudong New District, Shanghai 200131,China

View More >

CONTACT US

Tel: 021-50310528-801   
Phone: +86-17551581660
Skype: +86-17551581660 
QQ: 2737629806
Whatsapp: +86-17551581660
Email: support@wedobattery.com
Email: sales8@wedobattery.com

PRODUCT LIST

Sign up for our newsletter to receive the latest news.
​Copyright © 2023 WEDO. Sitemap.
Support By :Leadong.